Title
Low-cost monitoring system and partial discharge detection in cables
Date Issued
01 January 2022
Access level
metadata only access
Resource Type
conference paper
Publisher(s)
Institute of Electrical and Electronics Engineers Inc
Abstract
Partial discharge detection has been a challenge for electrical power systems and industrial automation; However, in recent years, with the evaluation of the state of non-intrusive electrical components and the detection of parasitic currents and high-frequency partial discharge, new mathematical developments and control systems for early detection have been allowed. In the present investigation, a sensor with 10 Rogowski coils is proposed; Mach - Machined, RSC - Rigid Split Core, RFC - Rigid Fixed Core, PCB, FCO - Openable Flex Core, FCF - Fixed Flex Core. Our findings are an accuracy for the partial discharge detection is 92.8% for voltage 220V for 10 A to 250A; during a time of 30 minutes; and an accuracy for the partial discharge detection is 81.2% for voltage 220V for 251 A to 350A; during a time of 30 minutes with comparison with effect Hall sensors and the disadvantage.
Language
English
OCDE Knowledge area
Ingeniería, Tecnología Ingeniería eléctrica, Ingeniería electrónica
Scopus EID
2-s2.0-85138770236
ISBN of the container
978-166548636-1
Conference
Proceedings of the 2022 IEEE 29th International Conference on Electronics, Electrical Engineering and Computing, INTERCON 2022
Sources of information: Directorio de Producción Científica Scopus